Let's Talk ↗
☰
EISAC AUTOMATION
REPAIR • TEST • RESTORE
REPAIR CASE STUDY SR-1898

Siemens SIRIUS 3RW44 Soft Starter 90 kW Repair

The Siemens SIRIUS 3RW44 Soft Starter is an industrial soft starter used to reduce motor starting current and mechanical stress in pumps, fans, compressors, conveyors and process machinery. This repair reference targets a representative 90 kW motor application; final soft-starter selection depends on motor full-load current, supply voltage, start duty and application conditions.

Brand Siemens
Equipment 3RW4427-1BC44
Equipment Category SIRIUS 3RW44 Soft Starter – 90 kW class
Industry Chemical
Fault Reported
  • Soft starter does not start the motor, trips during acceleration, shows phase/SCR/overload faults, or has control-board / power-stage malfunction.
Repair Turnaround Time Typical reference: 3–7 working days

The Challenge

A 90 kW motor-driven process could not start reliably, creating repeated production interruptions and risk of excessive mechanical and electrical stress.

Diagnosis

  • Control supply, input phases, thyristor/SCR power paths, bypass contactor, firing/gate circuits, current sensing, cooling system, HMI/control PCB, communication interface and motor/load conditions were inspected.

Our Solution

  • Power and control sections were diagnosed at component level; defective SCR/gate-driver/control components were replaced as required, cooling and bypass circuits were serviced, connections were restored, parameters were reviewed, and the starter was tested through repeated start/stop cycles.

Testing Performed

  • Control-power test; input-phase verification; SCR static test; gate/firing test; bypass operation test; motor start/stop test; current monitoring; communication check where fitted; thermal stability test; repeated-cycle run test.

Final Result

The reference repair process restores controlled motor starting and stopping after the unit passes electrical, power-stage, bypass, protection and functional run tests applicable to the starter.

Common Fault Codes & Causes

  • No Supply Voltage – Start command with missing mains, contactor timing or supply fault.
  • Phase Angle Control Fault – Incorrect motor wiring, inside-delta configuration, ground fault or unstable start parameters.
  • Current Limit Exceeded – Heavy load, incorrect current limit or start parameters.
  • Motor Overload – Excessive motor thermal loading or repeated starts.
  • Switching Element Fault – Thyristor/power semiconductor or gate-drive issue.
  • Bypass Fault – Bypass contactor/relay fails to close or opens unexpectedly.
  • Phase Failure – Missing/imbalanced mains phase or wiring issue.
  • Motor Temperature / Thermistor – Motor overtemperature or sensor/wiring problem.
  • Communication Fault – PROFIBUS/PROFINET/module configuration or network issue.
  • Device / Internal Fault – Internal electronics, control board, firmware or self-test failure.

Preventive Maintenance

  • Keep cooling paths clean, verify cabinet temperature, inspect line/motor terminals, check bypass contactor condition, confirm motor FLC and start-duty settings, protect the control supply, and investigate repeated phase/SCR/overload trips promptly.

Related Services

  • Industrial Electronics Repair; Soft Starter Repair; VFD Repair; Motor Control Repair; Control Board Repair; Power Electronics Repair

Need Professional Repair?

Contact Our Engineering Team Today
EISAC AUTOMATION
REPAIR • TEST • RESTORE
KEEPING INDUSTRY MOVING